Stc-600 Temperature Controller Manual Pdf _verified_ Jun 2026

| Parameter | Value | |-----------|-------| | Power Supply | 110V–220V AC / DC (50–60Hz) | | Display Range | -50°C to +120°C | | Control Range | -50°C to +120°C | | Measurement Accuracy | ±1°C | | Resolution | 0.1°C | | Sensor Type | NTC 10K (waterproof probe, length 2m) | | Relay Output 1 (Cooling) | 10A / 250V AC | | Relay Output 2 (Heating) | 10A / 250V AC | | Power Consumption | <3W | | Working Environment | -10°C to +60°C, RH <85% | | Dimensions | 75×34×85 mm (panel cutout: 71×29 mm) |

: Allows everyday users to adjust basic settings while keeping advanced system parameters (like high-level management adjustments) protected in a separate administrator menu. Stc-600 Temperature Controller Manual Pdf

: Protects the compressor by delaying its restart after reaching the set temperature (adjustable up to 15 minutes). | Parameter | Value | |-----------|-------| | Power

For full installation and safety details, refer to the STC-600 Instruction PDF provided by Bazanic. Do not exceed 10A load

Do not exceed 10A load. Use an external contactor for high-power devices (above 1000W).

| Problem | Possible Cause | Fix | |---------|----------------|-----| | No display | No power / wrong wiring | Check power input (1 & 2) | | Relay clicks but no output | Relay contacts worn | Use external contactor | | Temperature not accurate | Wrong sensor calibration | Adjust F3 calibration value | | Compressor cycles too fast | F4 delay too short | Increase F4 to 3–5 minutes |

According to the STC-600 Instruction Manual , wiring should follow these terminal identifications: : Connect the 220VAC power source. Sensor Input : Connect the NTC probe to the S1/S2 terminals.